500W Single Output Switching Power SupplySP-500 series

500W Single Output Switching Power Supply Features:
Universal AC input / Full range
Built-in active PFC function, PF>0.95
Protections: Short circuit/Over load/Over voltage/Over temperature
Forced air cooling by built-in DC fan
Built-in cooling Fan ON-OFF control
Built-in remote ON-OFF control
Built-in remote sense function
Fixed switching frequency at 110KHz
SPECIFICATION:
MODEL

SP-500-12

SP-500-13.5

SP-500-15

SP-500-24

SP-500-27

SP-500-48

OUTPUT DC VOLTAGE 12V 13.5V 15V 24V 27V 48V
RATED CURRENT 40A 36A 32A 20A 18A 10A
CURRENT RANGE 0 ~ 40A 0 ~ 36A 0 ~ 32A 0 ~ 20A 0 ~ 18A 0 ~ 10A
RATED POWER 480W 486W 480W 480W 486W 480W
RIPPLE & NOISE (max.) Note.2 240mVp-p 240mVp-p 240mVp-p 240mVp-p 200mVp-p 300mVp-p
VOLTAGE ADJ. RANGE 10 ~ 13.2V 12 ~ 15V 13.5 ~ 18V 20 ~ 26.4V 26 ~ 32V 41 ~ 56V
VOLTAGE TOLERANCE Note.3 ±1.0% ±1.0% ±1.0% ±1.0% ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
LOAD REGULATION ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%
SETUP, RISE, HOLD TIME 1500s, 50ms, 24ms
INPUT VOLTAGE RANGE 88 ~ 264VAC          124 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
POWER FACTOR PF>0.95/115       PF>0.95>240VAC at full load
EFFICIENCY (Typ.) 84% 84% 83% 85.5% 86.5% 87%
AC CURRENT 7A/115V        3.5A/230V
INRUSH CURRENT (max.) 18A/115V      36A/230V
LEAKAGE CURRENT <3.5mA / 240VAC
PROTECTION OVERLOAD 105 ~ 135% of rate load
Protection type: Fold back current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE 13.8 ~ 16.2V 15.5 ~ 18.2V 18 ~ 21V 27.6 ~ 32.4V 31 ~ 36.5V 57.6 ~ 67.2V
Protection type: Hiccup mode, recovers automatically after fault condition is removed.
FAN CONTROL,O.T.P. RTH1 or RTH2≧50ºC FAN ON,≦45ºC FAN, ≧70ºC output shut down
FUNCTION REMOTE CONTROL RC+/RC-:Short = power on ; Open = power off
ENVIRONMENT WORKING TEMP. -10 ~ +50ºC (Refer to output load derating curve), 20 ~ 90% RH non-condensing
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -20 ~ +85ºC, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/ºC (0 ~ 50ºC)
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC (Note.4) SAFETY STANDARDS Design refer to UL1950, TUV EN60950-1 
WITHSTAND VOLTAGE I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT Compliance to EN61000-3-2,-3
EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11;ENV50204,Light industry level,criteria A
OTHERS MTBF 133.4K hrs min. MIL-HDBK-217F (25ºC)
DIMENSION 170*120*93mm (L*W*H)
PACKING 1.807Kgs/pcs, 10pcs/19.53Kgs/0.0326CMB
NOTE 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3.Tolerance: includes set up tolerance, line regulation and load regulation.
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.