SPECIFICATION:
| MODEL |
D-120A |
D-120B |
| OUTPUT |
DC VOLTAGE |
5V |
12V |
5V |
24V |
| RATED CURRENT |
12A |
5A |
6A |
4A |
| CURRENT RANGE |
2 ~ 12A |
0.5 ~ 5A |
2 ~ 10A |
0.4 ~ 4A |
| RATED POWER |
120W |
126W |
| RIPPLE & NOISE (max.) Note.2 |
60mVp-p |
120mVp-p |
60mVp-p |
150mVp-p |
| VOLTAGE ADJ. RANGE |
CH1:4.75 ~ 5.5V |
| VOLTAGE TOLERANCE Note.3 |
±2.0% |
±6.0% |
±2.0% |
±7.0% |
| LINE REGULATION |
±0.5% |
±1.0% |
±0.5% |
±1.0% |
| LOAD REGULATION |
±0.5% |
±5.0% |
±0.5% |
±6.0% |
| SETUP, RISE, HOLD TIME |
200ms,50ms, 20ms at full load |
| INPUT |
VOLTAGE RANGE |
88 ~ 132VAC/176 ~ 264VAC selected by switch 248 ~ 370VDC |
| FREQUENCY RANGE |
47 ~ 63Hz |
| EFFICIENCY (Typ.) |
78% |
80% |
| AC CURRENT |
2.8A/115VAC 1.6A/230VAC |
| INRUSH CURRENT (max.) |
COLD START 35A |
| LEAKAGE CURRENT |
<3.5mA / 240VAC |
| PROTECTION |
OVERLOAD |
105 ~ 135% rated output power. |
| Protection type: Shut down o/p voltage, re-power on to recover. |
| OVER VOLTAGE |
CH1:5.75 ~ 6.75VDC |
| Protection type: Shut down o/p voltage, re-power on to recover. |
| ENVIRONMENT |
WORKING TEMP. |
-10 ~ +60ºC (Refer to output load derating curve) |
| WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
| STORAGE TEMP., HUMIDITY |
-20 ~ +85ºC, 10 ~ 95% RH |
| TEMP. COEFFICIENT |
±0.03%/ºC (0 ~ 50ºC) on +5V output |
| VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
| SAFETY & EMC (Note.4) |
SAFETY STANDARDS |
Design refer to UL1950, TUV EN60950-1 |
| WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| EMI CONDUCTION & RADIATION |
Compliance to EN55022 (CISPR22) Class B |
| HARMONIC CURRENT |
Compliance to EN61000-3-2,-3 |
| EMS IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, Light industry level, criteria A |
| OTHERS |
MTBF |
272.8K hrs min. MIL-HDBK-217F (25ºC) |
| DIMENSION |
199*110*50mm (L*W*H) |
| PACKING |
0.768Kg; 16pcs/13.92Kg/0.0287CMB |
| NOTE |
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |