SPECIFICATION:
| MODEL |
MDR-60-5 |
MDR-60-12 |
MDR-60-24 |
MDR-60-48 |
| OUTPUT |
DC VOLTAGE |
5V |
12V |
24V |
48V |
| RATED CURRENT |
10A |
5A |
2.5A |
1.25A |
| CURRENT RANGE |
0 ~ 10A |
0 ~ 5A |
0 ~ 2.5A |
0 ~ 1.25A |
| RATED POWER |
50W |
60W |
60W |
60W |
| RIPPLE & NOISE (max.) Note.2 |
80mVp-p |
120mVp-p |
150mVp-p |
200mVp-p |
| VOLTAGE ADJ. RANGE |
5 ~ 6V |
12 ~ 15V |
24 ~ 30V |
48 ~ 56V |
| VOLTAGE TOLERANCE Note.3 |
±2.0% |
±1.0% |
±1.0% |
±1.0% |
| LINE REGULATION |
±1.0% |
±1.0% |
±1.0% |
±1.0% |
| LOAD REGULATION |
±15% |
±1.0% |
±1.0% |
±1.0% |
| SETUP, RISE TIME |
500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load |
| HOLD TIME(Typ.) |
50ms/230VAC 20ms/115VAC at full load |
| INPUT |
VOLTAGE RANGE |
85 ~ 264VAC 120 ~ 370VDC |
| FREQUENCY RANGE |
47 ~ 63Hz |
| EFFICIENCY (Typ.) |
78% |
86% |
88% |
87% |
| AC CURRENT |
1.8A/115VAC 1A/230VAC |
| INRUSH CURRENT(max.) |
COLD START 30A/115VAC 60A/230VAC |
| PROTECTION |
OVERLOAD |
105 ~ 150% rated output power |
| Protection type: Constant current limiting,recovers automatically after fault condition is removed |
| OVER VOLTAGE |
6.25 ~ 7.25V |
15.6 ~ 18V |
31.2 ~ 36V |
57.6 ~ 64.8V |
| Protection type: Shut down o/p voltage,re-power on to recover |
| FUNCTION |
DC OK ACTIVE SIGNAL (max.) |
Relay contact rating(max.): 30V/1A resistive |
| ENVIRONMENT |
WORKING TEMP. |
-20 ~ +70ºC (Refer to output load derating curve) |
| WORKING HUMIDITY |
20 ~ 90% RH non-condensing |
| STORAGE TEMP., HUMIDITY |
-40 ~ +85ºC, 10 ~ 95% RH |
| TEMP. COEFFICIENT |
±0.03%/ºC (0 ~ 50ºC) |
| VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
| SAFETY & EMC (Note.4) |
SAFETY STANDARDS |
Design refer to UL508, TUV EN60950-1 |
| WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| EMI CONDUCTION & RADIATION |
Compliance to EN55022 (CISPR22) Class B |
| HARMONIC CURRENT |
Compliance to EN61000-3-2,-3 |
| EMS IMMUNITY |
Compliance to EN61000-4-2,3,4,5; ENV50204, EN55024, Light industry level, criteria A |
| OTHERS |
MTBF |
229.2K hrs min. MIL-HDBK-217F (25ºC ) |
| DIMENSION |
40*90*100mm (W*H*D) |
| PACKING |
0.33Kg; 42pcs/14.8Kg/0.82CUFT |
| NOTE |
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. 5.Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time. |