75W Industrial DIN-Rail Power SupplyDR-75 series

75W Industrial DIN-Rail Power Supply Features:
Universal AC input/Full range
Protections: Short circuit/Over load/Over voltage/Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
LED indicator for power on
100% full load burn-in test
Fix switching frequency at 50KHz
SPECIFICATION:
MODEL

DR-75-12

DR-75-24

DR-75-48

OUTPUT DC VOLTAGE 12V 24V 48V
RATED CURRENT 6.3A 3.2A 1.6A
CURRENT RANGE 0 ~ 6.3A 0 ~ 3.2A 0 ~ 1.6A
RATED POWER 76W 76.8W 76.8W
RIPPLE & NOISE (max.) Note.2 100mVp-p 150mVp-p 240mVp-p
VOLTAGE ADJ. RANGE 12 ~ 14V 24 ~ 28V 48 ~ 53V
VOLTAGE TOLERANCE Note.3 ±2.0% ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5% ±0.5%
LOAD REGULATION ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME 1000ms, 60ms/230VAC   1800ms, 60ms/115VAC    at full load
HOLD TIME(Typ.) 60ms/230VAC      12ms/115VAC  at full load
INPUT VOLTAGE RANGE 85 ~ 264VAC       120 ~ 370VDC
FREQUENCY RANGE 47 ~ 63Hz
EFFICIENCY (Typ.) 76% 80% 81%
AC CURRENT 1.6A/115VAC     0.96A/230VAC
INRUSH CURRENT(max.) COLD START 20A/115VAC 40A/230VAC
LEAKAGE CURRENT <1mA/240VAC
PROTECTION OVERLOAD 105 ~ 150% rated output power
Protection type: Constant current limiting,recovers automatically after fault condition is removed
OVER VOLTAGE 15 ~ 16.5V 29 ~ 34V 58 ~ 65V
Protection type: Hiccup mode, recovers automatically after fault condition is removed
OVER TEMPERATURE 85ºC±5ºC (TSW1) Detect on heat sink of power transistor
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down
ENVIRONMENT WORKING TEMP. -10 ~ +60ºC (Refer to output load derating curve)
WORKING HUMIDITY 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY -20 ~ +85ºC, 10 ~ 95% RH
TEMP. COEFFICIENT ±0.03%/ºC (0 ~ 50ºC)
VIBRATION 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY & EMC (Note.4) SAFETY STANDARDS Design refer to UL508,TUV EN60950-1
WITHSTAND VOLTAGE I/P-O/P:3KVAC     I/P-FG:1.5KVAC     O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT Compliance to EN61000-3-2,-3
EMS IMMUNITY Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A
OTHERS MTBF 123.1K hrs min. MIL-HDBK-217F (25ºC)
DIMENSION 55.5*125.2*100mm (L*W*H)
PACKING 0.6Kg; 20pcs/13Kg/1.1CUFT
NOTE 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature.
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3.Tolerance: includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.