SPECIFICATION:
| MODEL |
DR-150-12 |
DR-150-15 |
DR-150-24 |
DR-150-48 |
| OUTPUT |
DC VOLTAGE |
12V |
15V |
24V |
48V |
| RATED CURRENT |
12.5A |
10A |
6.3A |
3.1A |
| CURRENT RANGE |
0 ~ 12.5A |
0 ~ 10A |
0 ~ 6.3A |
0 ~ 3.1A |
| RATED POWER |
150W |
150W |
151.2W |
148.8W |
| RIPPLE & NOISE (max.) Note.2 |
120mVp-p |
150mVp-p |
150mVp-p |
200mVp-p |
| VOLTAGE ADJ. RANGE |
10.8 ~ 13.2V |
13.5 ~ 16.5V |
21.6 ~ 26.4V |
43.2 ~ 52.8V |
| VOLTAGE TOLERANCE Note.3 |
±2.0% |
±1.0% |
±1.0% |
±1.0% |
| LINE REGULATION |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
| LOAD REGULATION |
±0.5% |
±0.5% |
±0.5% |
±0.5% |
| SETUP, RISE TIME |
500ms, 50ms/230VAC 500ms, 50ms/115VAC at full load |
| HOLD TIME(Typ.) |
20ms/230VAC 18ms/115VAC at full load |
| INPUT |
VOLTAGE RANGE |
85 ~ 132VAC / 170 ~ 264VAC Auto switch 248 ~ 370VDC |
| FREQUENCY RANGE |
47 ~ 63Hz |
| EFFICIENCY (Typ.) |
82% |
83% |
85% |
86% |
| AC CURRENT |
2.6A/115VAC 1.6A/230VAC |
| INRUSH CURRENT(max.) |
COLD START 40A/230VAC |
| LEAKAGE CURRENT |
<0.7mA/240VAC |
| PROTECTION |
OVERLOAD |
110 ~ 130% rated output power |
| Protection type: Shut down o/p voltage, re-power on to recover |
| OVER VOLTAGE |
15 ~ 16.5V |
17.25 ~ 20.25V |
29 ~ 33V |
58 ~ 65V |
| Protection type: Shut down o/p voltage, re-power on to recover |
| ENVIRONMENT |
WORKING TEMP. |
'-10 ~ +50ºC (Refer to output load derating curve) |
| WORKING HUMIDITY |
20 ~ 93% RH non-condensing |
| STORAGE TEMP., HUMIDITY |
-20 ~ +85ºC, 10 ~ 95% RH |
| TEMP. COEFFICIENT |
±0.03%/ºC (0 ~ 50ºC) |
| VIBRATION |
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes |
| SAFETY & EMC (Note.4) |
SAFETY STANDARDS |
Design refer to UL508, UL60950-1, TUV EN60950-1 |
| WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC |
| ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC |
| EMI CONDUCTION & RADIATION |
Compliance to EN55011,EN55022 (CISPR22) Class B |
| HARMONIC CURRENT |
Compliance to EN61000-3-2,-3 |
| EMS IMMUNITY |
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2) Heavy industry level, criteria A |
| OTHERS |
MTBF |
136.8K hrs min. MIL-HDBK-217F (25ºC) |
| DIMENSION |
108.4*83.6*109mm (L*W*H) |
| PACKING |
0.79Kg; 20pcs/16.5Kg/1.1CUFT |
| NOTE |
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25ºC of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |